The module communicates and is powered via the control panel bus. It can be installed in JA-19xPL installation boxes or the control panel box.
It is not addressable (does not occupy any position in the security system).
Power supply | via the control panel bus 12 V (9 ...15 V) |
---|---|
Current consumption during backup (open/closed relay) | 5 mA/25 mA |
Current consumption for cable selection | 25 mA |
Loading capacity of the relay contacts: | |
Max. switched voltage | 50 V AC/60 V DC |
Maximum switched current | max. 2 A |
Minimum switched current | 10 mA |
Dimensions | 70 x 40 x 15 mm |
Classification | level 2 in acc. with EN 50131-1, EN 50131-3 only when module is located in a JA-194PL or JA-195PL box using the JA-111H TRB module |
Environment according to | EN 50131-1 II. indoor, general |
Operation temperature range | -10 °C to +40 °C |
It also meets the requirements of | EN 50130-4 ed. 2+A1, EN 55032, ČSN EN 50581 |