It features switching contacts with galvanic and safety isolation for the switching of 230 V AC/16 A power loads, which can be used in one of eight selectable modes. The relay is designed for installation on a DIN rail and its characteristics are set with the use of switches under a cover.
It offers 8 functions:
Power supply | 230 V AC / 50 Hz, protective class II. |
---|---|
Power consumption | 0.3 W / max. 0.8 W |
Input A | 230 V AC |
Loading capacity of the power relay contacts: | |
(galvanically isolated from the control terminals) | protection class II: |
Max. switched voltage | 250 V AC / 24 V DC |
Resistive load (cosφ=1) | max. 16 A |
Inductive, capacitive load (cosφ=0.4) | max. 8 A |
Halogen lighting | max. 1000 W |
Direct current (DC) | 384 W |
Minimum switched DC power | 0.5 W |
Wire cross section | max. 2 x 1.5 mm2; max. 1 x 2.5 mm2 |
Dimensions | 18 x 90 x 65 mm, 1 DIN module |
Operating temperature range | -10 to +40 °C |
Ingress protection class | IP20, IP40 for the front panel (EN 60529) |
In conformity with | EN 60947-6-1, EN 61000-6-1, EN 50581 |