The JA-110ST bus fire detector (optical and temperature detection) detects fire in residential and commercial buildings . Allows you to set detection: optical and thermal, optical or thermal, optical only or temperature only.
The detector is addressable, and occupies one position in an alarm system.
SMART MEMORY indictaion (SMI) provides a visual (LED) verification of detector triggering. SMI is reset via the keypad. P>
| Power | 12 V bus (9 ... 15 V) |
|---|---|
| Current consumption in standby (quiescent) | 5 mA |
| Current consumption for choice of cable | 10 mA |
| Dimensions | diameter 126 mm, height 50 mm |
| Smoke detection | optical dispersion |
| Sensitivity of smoke detector | m = 0.11 ¸ 0.13 dB / m according to DIN EN 54-7 |
| Temperature detection | class A2 according to DIN EN 54-5 |
| Alarm Temperature | +60 ° C to +70 ° C td> |
| Operating temperature range | -10 ° C to +80 ° C |
| Meets | EN 54-5, EN 54-7, EN 50130-4, EN 55022 |